Go to frontpage


 

Alfa Laval Aalborg OM

________________________________________________________________________________________

 

General

 

  • Vertical cylindrical boiler made of mild steel
  • Standard preassembled boiler unit
  • Integrated control panel
  • Pin tube elements
  • Top-mounted fittings
  • Ready to install
  • Designed for operation with a monobloc type pressure jet or rotary cup burner

 

Design data

 

Thermal output: up to 4.6 MW
Steam capacity: 1.6 - 6.5 t/h
Design pressure: up to 11 bar(g)

 

 

Description

 

The boiler is available as a steam boiler in capacities up to 45 t/h or as a hot-water boiler (Aalborg CHS) in capacities up to 30 MW.


The boiler consists of a furnace and a convection part integrated with the steam drum. The flue gas flows vertically from the furnace up through the pin element tubes in the drum to the flue gas box at the
top of the boiler.

 

The boiler is side-fired, which makes the boiler very easy to ventilate and gives an operation and maintenance friendly location of the burner and
its controls.


It is ideal for installation on deck.

 

   

 

Capacity, Fuel economy, Dimensions & Weight


                 
                 
                 
                 
                 
                 
                 
Steam capacity

Design pressure

Thermal output at 100% MCR

Height "H"

Diameter "D" (incl. insulation)

Height "H"

*

Width "B"

Boiler dry weight

Boiler operation weight

kg/h

bar(g)

kW

mm

mm

mm

mm

ton

ton

8,000

11

5,600

6,600

2,470

3,670

2,820

16.6

22.2

10,000

11

7,000

6,720

2,620

3,960

3,020

18.8

25.0

12,500

11

8,800

6,720

2,920

4,260

3,270

22.4

30.2

16,000

11

11,200

7,400

3,120

4,460

3,470

26.5

35.2

20,000

11

14,000

7,450

3,520

4,860

3,870

31.6

43.0


* With Aalborg KB rotary cup burner.






Steam capacity

Design pres- sure

Thermal output at 100% MCR

Height "H" 

Dia- meter "D" (incl. insula tion)

Width "W1" Heating coil removal

Width "W2" Burner removal *

Flue gas outlet con- nected

Boiler dry weight
**

Water volume

kg/h

bar(g)

kW

mm

mm

mm

mm

DN

ton

ton

14,000

18

9.8

7,300

3,000

2,015

3,320

700

19.0

8.3

16,000

18

11.2

7,800

3,000

2,015

3,440

700

20.3

8.1

20,000

18

14.0

7,900

3,300

2,165

3,595

900

24.7

10.0

25,000

18

17.5

8,700

3,300

2,165

3,820

900

27.0

10.5

30,000 18 21.0 9,000 3,600 2,315 4,000 1,000 32.9 12.6
35,000 18 24.5 9,620 3,900 2,465 4,775 1,000 38.4 15.1
40,000 18 28.0 9,660 4,100 2,565 4,735 1,200 43.3 16.6
45,000 18 31.5 9,660 4,100 2,565 5,690 1,200 45.7 17.0

 

* With Aalborg KBSA steam atomizing burner.
** Without burner and accessories.
Capacity 45,000 kg/h is with extended furnace.

 

 

DATA SHEET series
© Aalborg Industries, rev.: 4.0, April 2009 (Design data are subject to change without prior notice).

 

________________

 

Related material:



© Alfa Laval Aalborg A/S | Gasvaerksvej 24 | 9100 Aalborg | Denmark | Terms »